022-1HB10 - Signal modules digital | Digital output modules
Order no. |
022-1HB10 |
Type | SM 022 |
Module ID | 0109 AF90 |
General information | |
Note | - |
Features | 2x DO DC 30 V AC 230 V 3 A Potential separated per channel Relay |
Current consumption/power loss |
|
Current consumption from backplane bus | 120 mA |
Power loss | 0.7 W |
Technical data digital outputs | |
Number of outputs | 2 |
Cable length, shielded | 1000 m |
Cable length, unshielded | 600 m |
Rated load voltage | DC 30 V/ AC 230 V |
Current consumption from load voltage L+ (without load) | - |
Total current per group, horizontal configuration, 40°C | 3 A |
Total current per group, horizontal configuration, 60°C | 3 A |
Total current per group, vertical configuration | 3 A |
Output current at signal "1", rated value | 3 A |
Signal logic output | Isolated |
Output delay of "0" to "1" | 10 ms |
Output delay of "1" to "0" | 5 ms |
Minimum load current | - |
Lamp load | - |
Parallel switching of outputs for redundant control of a load | not possible |
Parallel switching of outputs for increased power | not possible |
Actuation of digital input | - |
Switching frequency with resistive load | max. 0.33 Hz |
Switching frequency with inductive load | max. 0.33 Hz |
Switching frequency on lamp load | max. 0.33 Hz |
Internal limitation of inductive shut-off voltage | - |
Short-circuit protection of output | - |
Trigger level | - |
Number of operating cycle of relay outputs | - |
Switching capacity of contacts | 3 A |
Output data size | 2 Bit |
Status information, alarms, diagnostics |
|
Status display | green LED per channel |
Interrupts | no |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | no |
Diagnostics information read-out | none |
Supply voltage display | green LED |
Group error display | red LED |
Channel error display | none |
Isolation |
|
Between channels | ![]() |
Between channels of groups to | - |
Between channels and backplane bus | ![]() |
Insulation tested with | AC 2200 V |
PWM data | |
PWM channels | - |
PWM time basis | - |
Period length | - |
Minimum pulse width | - |
Type of output | - |
Safety | |
Safety protocol | - |
Safety requirements | - |
Secure user address | - |
Watchdog | - |
Two channels | - |
Test pulse length | - |
Circuit monitoring | - |
Datasizes | |
Input bytes | 0 |
Output bytes | 1 |
Parameter bytes | 0 |
Diagnostic bytes | 0 |
Housing |
|
Material | PPE / PPE GF10 |
Mounting | Profile rail 35 mm |
Mechanical data | |
Dimensions (WxHxD) | 12.9 mm x 109 mm x 76.5 mm |
Net weight | 62 g |
Weight including accessories | 62 g |
Gross weight | 76 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications | |
UL certification | yes |
KC certification | yes |