Skip to main content
  • MICRO PLC

M31-1CD50 - Signal modules analog | Analog input modules

Order no.

M31-1CD50

TypeSM M31
Module ID0417 1544

General information

Note-
Features4x AI
16 Bit
Voltage 0...10 V, -10 V…+10 V
Current 0/4...20 mA
Resistance 0....3000 Ohm, RTD, Pt100, Pt1000, NI100, NI1000 in 2/3/4 conductor measurement
TC type J, K, N, R, S, T, B, C, E, L and U +/-80 mV

Current consumption/power loss

Current consumption from backplane bus150 mA
Power loss750 mW

Technical data analog inputs

Number of inputs4
Cable length, shielded200 m
Rated load voltage-
Current consumption from load voltage L+ (without load)-
Voltage inputs
Min. input resistance (voltage range)100 kΩ
Input voltage ranges0 V ... +10 V
-10 V ... +10 V
-80 mV ... +80 mV
Operational limit of voltage ranges+/-0.3%
Operational limit of voltage ranges with SFU+/-0.3%
Basic error limit voltage ranges+/-0.2%
Basic error limit voltage ranges with SFU+/-0.2%
Destruction limit voltagemax. 30V
Current inputs
Max. input resistance (current range)70 Ω
Input current ranges0 mA ... +20 mA
+4 mA ... +20 mA
Operational limit of current ranges+/-0.3%
Operational limit of current ranges with SFU+/-0.3%
Basic error limit current ranges+/-0.2%
Radical error limit current ranges with SFU+/-0.2%
Destruction limit current inputs (voltage)max. 30V
Destruction limit current inputs (electrical current)max. 60mA
Resistance inputs
Resistance ranges0 ... 60 Ohm
0 ... 600 Ohm
0 ... 3000 Ohm
Operational limit of resistor ranges+/-0.3%
Operational limit of resistor ranges with SFU+/-0.3%
Basic error limit+/-0.2%
Basic error limit with SFU+/-0.2%
Destruction limit resistance inputsmax. 30V
Resistance thermometer inputs
Resistance thermometer rangesPt100
Pt1000
Ni100
Ni1000
Operational limit of resistance thermometer ranges+/-0.3%
Operational limit of resistance thermometer ranges with SFU+/-0.3%
Basic error limit thermoresistor ranges+/-0.2%
Basic error limit thermoresistor ranges with SFU+/-0.2%
Destruction limit resistance thermometer inputsmax. 30V
Thermocouple inputs
Thermocouple rangestype J
type L
type K
type N
type R
type S
type B
type C
type E
type T
Operational limit of thermocouple rangesfor type B: +/-14.6K; for type K, for type N: +/-1.,0K; for type S, for type R: +/-14.1K; for type T: +/-12.0K; for type C: +/-14.0K; for type E: +/-13.0K; for type J: +/-11.0K; for type L: +/-13.5K
Operational limit of thermocouple ranges with SFUfor type B: +/-14.6K; for type K, Typ N: +/-10.0K; for type S, for type R: +/-14.1K; for type T: +/-12.0K; for type C: +/-14.0K; for type E: +/-13.0K; for type J: +/-11.0K; for type L: +/-13.5K
Basic error limit thermoelement rangesfor type B: +/-14.6K; for type K, type N: +/-10.0K; for type S, for type R: +/-14.1K; for type T: +/-12.0K; for type C: +/-14.0K; for type E: +/-13.0K; for type J: +/-11.0K; for type L: +/-13.5K
Basic error limit thermoelement ranges with SFUfor type B: +/-14.6K; for type K, Typ N: +/-10.0K; for type S, type R: +/-14.1K; for type T: +/-12.0K; for type C: +/-14.0K; for type E: +/-13.0K; for type J: +/-11.0K; for type L: +/-13.5K
Destruction limit thermocouple inputsmax. 30V
Programmable temperature compensation-
External temperature compensation-
Internal temperature compensation
Temperature error internal compensation8 K
Technical unit of temperature measurement°C, °F, K
Resolution in bit16
Measurement principleSigma-Delta
Basic conversion time10ms … 200ms (for R/RTD & TC)
Noise suppression for frequency>80dB (UCM <3,2V)

Status information, alarms, diagnostics

Status displayBicolour green/red LED
Interruptsyes, parameterizable
Process alarmyes, parameterizable
Diagnostic interruptyes, parameterizable
Diagnostic functionsyes, parameterizable
Diagnostics information read-outpossible
Module statenone
Module error displayBicolour green/red LED
Channel error displayred LED per channel

Isolation

Between channels
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply-
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)DC 3 V
Max. potential difference between Mana and Mintern (Uiso)DC 75 V/ AC 50 V
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)-
Max. potential difference between Mintern and outputs-
Insulation tested with-

Datasizes

Input bytes8
Output bytes0
Parameter bytes32
Diagnostic bytes20

Housing

MaterialPPE / PPE GF10
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)26 mm x 88 mm x 71 mm
Net weight88 g
Weight including accessories88 g
Gross weight105 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-40 °C to 70 °C

Certifications

UL certificationin preparation
KC certificationin preparation

Downloads

[Fiche technique]
[Manual]