Skip to main content
  • 200V

250-1BS00 - Function modules | SSI modules

Order no.

250-1BS00

TypeFM 250S

General information

Note-
Features1 SSI channel
RS422
12/24 Bit
Direct power supply to the SSI transducer
Baud rate: 100/300/600 Kbit/s (default: 300 Kbit/s)
2x parameterizable DO, DC 24 V, 1 A
One may be used as hold input

Current consumption/power loss

Current consumption from backplane bus120 mA
Power loss1 W

Technical data digital inputs

Number of inputs1
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)5 mA
Rated valueDC 20.4...28.8 V
Input voltage for signal "0"DC 0...5 V
Input voltage for signal "1"DC 15...28.8 V
Input voltage hysteresis-
Frequency range-
Input resistance-
Input current for signal "1"7 mA
Connection of Two-Wire-BEROs possible-
Max. permissible BERO quiescent current-
Input delay of "0" to "1"3 ms
Input delay of "1" to "0"3 ms
Number of simultaneously utilizable inputs horizontal configuration1
Number of simultaneously utilizable inputs vertical configuration1
Input characteristic curveIEC 61131-2, type 1
Initial data size4 Byte

Technical data digital outputs

Number of outputs2
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)5 mA
Total current per group, horizontal configuration, 40°C2 A
Total current per group, horizontal configuration, 60°C2 A
Total current per group, vertical configuration2 A
Output voltage signal "1" at min. currentL+ (-0.8 V)
Output voltage signal "1" at max. currentL+ (-125 mV)
Output current at signal "1", rated value1 A
Output current, permitted range to 40°C-
Output current, permitted range to 60°C-
Output current at signal "0" max. (residual current)-
Output delay of "0" to "1"max. 100 µs
Output delay of "1" to "0"max. 350 µs
Minimum load current-
Lamp load5 W
Parallel switching of outputs for redundant control of a loadnot possible
Parallel switching of outputs for increased powernot possible
Actuation of digital input-
Switching frequency with resistive loadmax. 1000 Hz
Switching frequency with inductive loadmax. 0.5 Hz
Switching frequency on lamp loadmax. 10 Hz
Internal limitation of inductive shut-off voltageL+ (-52 V)
Short-circuit protection of outputyes, electronic
Trigger level1.8 A
Number of operating cycle of relay outputs-
Switching capacity of contacts-
Output data size4 Byte

Status information, alarms, diagnostics

Status displayyes
Interruptsno
Process alarmno
Diagnostic interruptno
Diagnostic functionsno
Diagnostics information read-outnone
Supply voltage displayyes
Group error displayyes
Channel error displaynone

Isolation

Between channels-
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply-
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)-
Max. potential difference between Mana and Mintern (Uiso)-
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)-
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Technical data SSI

Interfaces typeRS422
Encoder frequency / baud rateparameterizable (100k, 300kHz)
SSI pause time35µs
Normalization-
Bit length encoder data24 Bit
Mode master
Mode monitoring operation-
Shift direction MSB first
Shift direction LSB first-
Binary code
Gray code

Datasizes

Input bytes4
Output bytes4
Parameter bytes6
Diagnostic bytes0

Housing

MaterialPPE / PA 6.6
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)25.4 mm x 76 mm x 78 mm
Net weight100 g
Weight including accessories-
Gross weight-

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certification-

Downloads

[Datasheet]
[Manual]