031-1BD80 - Signal modules analog | Analog input modules
Order no. |
031-1BD80 |
Type | SM 031 |
Module ID | 0406 1544 |
General information | |
Note | - |
Features | 4x AI 16 Bit Resistance 0…3000 Ohm Resistance measurement with 2-, 3- and 4-wires Resistance temperature transmitter Pt100, Pt1000, NI100 und NI1000 |
Current consumption/power loss |
|
Current consumption from backplane bus | 85 mA |
Power loss | 1 W |
Technical data analog inputs | |
Number of inputs | 4 |
Cable length, shielded | 200 m |
Rated load voltage | DC 24 V |
Current consumption from load voltage L+ (without load) | 30 mA |
Voltage inputs | - |
Min. input resistance (voltage range) | - |
Input voltage ranges | - |
Operational limit of voltage ranges | - |
Operational limit of voltage ranges with SFU | - |
Basic error limit voltage ranges | - |
Basic error limit voltage ranges with SFU | - |
Destruction limit voltage | - |
Current inputs | - |
Max. input resistance (current range) | - |
Input current ranges | - |
Operational limit of current ranges | - |
Operational limit of current ranges with SFU | - |
Basic error limit current ranges | - |
Radical error limit current ranges with SFU | - |
Destruction limit current inputs (voltage) | - |
Destruction limit current inputs (electrical current) | - |
Resistance inputs | |
Resistance ranges | 0 ... 60 Ohm 0 ... 600 Ohm 0 ... 3000 Ohm |
Operational limit of resistor ranges | +/- 0.4 % |
Operational limit of resistor ranges with SFU | +/- 0,2 % |
Basic error limit | +/- 0.2 % |
Basic error limit with SFU | +/- 0,1 % |
Destruction limit resistance inputs | max. 24V |
Resistance thermometer inputs | |
Resistance thermometer ranges | Pt100 Pt1000 Ni100 Ni1000 |
Operational limit of resistance thermometer ranges | +/- 0.4 % |
Operational limit of resistance thermometer ranges with SFU | +/- 0,2 % |
Basic error limit thermoresistor ranges | +/- 0.2 % |
Basic error limit thermoresistor ranges with SFU | +/- 0,1 % |
Destruction limit resistance thermometer inputs | max. 24V |
Thermocouple inputs | - |
Thermocouple ranges | - |
Operational limit of thermocouple ranges | - |
Operational limit of thermocouple ranges with SFU | - |
Basic error limit thermoelement ranges | - |
Basic error limit thermoelement ranges with SFU | - |
Destruction limit thermocouple inputs | - |
Programmable temperature compensation | - |
External temperature compensation | - |
Internal temperature compensation | - |
Temperature error internal compensation | - |
Technical unit of temperature measurement | °C, °F, K |
Resolution in bit | 16 |
Measurement principle | Sigma-Delta |
Basic conversion time | 4.2...324.1 ms (50 Hz) 3.8...270.5 ms (60 Hz) per channel |
Noise suppression for frequency | >80dB at 50Hz (UCM<6V) |
Status information, alarms, diagnostics | |
Status display | yes |
Interrupts | yes, parameterizable |
Process alarm | yes, parameterizable |
Diagnostic interrupt | yes, parameterizable |
Diagnostic functions | yes |
Diagnostics information read-out | possible |
Module state | green LED |
Module error display | red LED |
Channel error display | red LED per channel |
Isolation | |
Between channels | - |
Between channels of groups to | - |
Between channels and backplane bus | |
Between channels and power supply | - |
Max. potential difference between circuits | - |
Max. potential difference between inputs (Ucm) | DC 6 V |
Max. potential difference between Mana and Mintern (Uiso) | - |
Max. potential difference between inputs and Mana (Ucm) | - |
Max. potential difference between inputs and Mintern (Uiso) | DC 75 V/ AC 50 V |
Max. potential difference between Mintern and outputs | - |
Insulation tested with | DC 500 V |
Technical data encoder supply | |
Number of outputs | - |
Output voltage (typ) | - |
Output voltage (rated value) | - |
Short-circuit protection | - |
Binding of potential | - |
Datasizes | |
Input bytes | 8 |
Output bytes | 0 |
Parameter bytes | 34 |
Diagnostic bytes | 20 |
Housing |
|
Material | PPE / PPE GF10 |
Mounting | Profile rail 35 mm |
Mechanical data | |
Dimensions (WxHxD) | 12.9 mm x 109 mm x 76.5 mm |
Net weight | 61 g |
Weight including accessories | 61 g |
Gross weight | 75 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications | |
UL certification | yes |
KC certification | yes |