031-1BF60 - Signal modules analog | Analog input modules
Order no. | 031-1BF60 |
Type | SM 031 |
Module ID | 0416 15C5 |
General information |
|
Note | - |
Features | 8x AI single ended (reference potential 0V) 12 Bit Current 0(4)...20 mA Separate parameterizable inputs Isolated opposite backplane bus |
Current consumption/power loss | |
Current consumption from backplane bus | 70 mA |
Power loss | 1 W |
Technical data analog inputs |
|
Number of inputs | 8 |
Cable length, shielded | 200 m |
Rated load voltage | DC 24 V |
Current consumption from load voltage L+ (without load) | 20 mA |
Voltage inputs | - |
Min. input resistance (voltage range) | - |
Input voltage ranges | - |
Operational limit of voltage ranges | - |
Operational limit of voltage ranges with SFU | - |
Basic error limit voltage ranges | - |
Basic error limit voltage ranges with SFU | - |
Destruction limit voltage | - |
Current inputs | |
Max. input resistance (current range) | 60 Ω |
Input current ranges | 0 mA ... +20 mA +4 mA ... +20 mA |
Operational limit of current ranges | +/-0.5% |
Operational limit of current ranges with SFU | - |
Basic error limit current ranges | +/-0.3% |
Radical error limit current ranges with SFU | - |
Destruction limit current inputs (voltage) | max. 30V |
Destruction limit current inputs (electrical current) | max. 40mA |
Resistance inputs | - |
Resistance ranges | - |
Operational limit of resistor ranges | - |
Operational limit of resistor ranges with SFU | - |
Basic error limit | - |
Basic error limit with SFU | - |
Destruction limit resistance inputs | - |
Resistance thermometer inputs | - |
Resistance thermometer ranges | - |
Operational limit of resistance thermometer ranges | - |
Operational limit of resistance thermometer ranges with SFU | - |
Basic error limit thermoresistor ranges | - |
Basic error limit thermoresistor ranges with SFU | - |
Destruction limit resistance thermometer inputs | - |
Thermocouple inputs | - |
Thermocouple ranges | - |
Operational limit of thermocouple ranges | - |
Operational limit of thermocouple ranges with SFU | - |
Basic error limit thermoelement ranges | - |
Basic error limit thermoelement ranges with SFU | - |
Destruction limit thermocouple inputs | - |
Programmable temperature compensation | - |
External temperature compensation | - |
Internal temperature compensation | - |
Temperature error internal compensation | - |
Technical unit of temperature measurement | - |
Resolution in bit | 12 |
Measurement principle | successive approximation |
Basic conversion time | 2 ms all channels |
Noise suppression for frequency | >50dB at 50Hz (UCM<2V) |
Status information, alarms, diagnostics |
|
Status display | yes |
Interrupts | no |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | yes |
Diagnostics information read-out | possible |
Module state | green LED |
Module error display | red LED |
Channel error display | red LED per channel |
Isolation |
|
Between channels | - |
Between channels of groups to | - |
Between channels and backplane bus | |
Between channels and power supply | - |
Max. potential difference between circuits | - |
Max. potential difference between inputs (Ucm) | - |
Max. potential difference between Mana and Mintern (Uiso) | - |
Max. potential difference between inputs and Mana (Ucm) | - |
Max. potential difference between inputs and Mintern (Uiso) | DC 75 V/ AC 50 V |
Max. potential difference between Mintern and outputs | - |
Insulation tested with | DC 500 V |
Technical data encoder supply |
|
Number of outputs | - |
Output voltage (typ) | - |
Output voltage (rated value) | - |
Short-circuit protection | - |
Binding of potential | - |
Datasizes |
|
Input bytes | 16 |
Output bytes | 0 |
Parameter bytes | 14 |
Diagnostic bytes | 20 |
Housing | |
Material | PPE / PPE GF10 |
Mounting | Profile rail 35 mm |
Mechanical data |
|
Dimensions (WxHxD) | 12.9 mm x 109 mm x 76.5 mm |
Net weight | 58 g |
Weight including accessories | 58 g |
Gross weight | 73 g |
Environmental conditions | |
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | yes |
KC certification | yes |