032-1BB40 - Signal modules analog | Analog output modules
Order no. |
032-1BB40 |
Type | SM 032 |
Module ID | 0502 25D8 |
General information | |
Note | - |
Features | 2x AO 12 Bit Current 0(4)…20 mA |
Current consumption/power loss |
|
Current consumption from backplane bus | 85 mA |
Current consumption from load voltage L+ (without load) | 15 mA |
Power loss | 0.8 W |
Technical data analog outputs |
|
Number of outputs | 2 |
Cable length, shielded | 200 m |
Rated load voltage | DC 24 V |
Reverse polarity protection of rated load voltage | |
Current consumption from rated load voltage | - |
Voltage output short-circuit protection | - |
Voltage outputs | - |
Min. load resistance (voltage range) | - |
Max. capacitive load (current range) | - |
Max. inductive load (current range) | - |
Output voltage ranges | - |
Operational limit of voltage ranges | - |
Basic error limit voltage ranges | - |
Destruction limit against external applied voltage | - |
Current outputs | |
Max. in load resistance (current range) | 350 Ω |
Max. inductive load (current range) | 10 mH |
Typ. open circuit voltage current output | 12 V |
Output current ranges | 0 mA ... +20 mA +4 mA ... +20 mA |
Operational limit of current ranges | +/-0.4% ... +/-0.5% |
Basic error limit current ranges | +/-0.2% ... +/-0.3% |
Destruction limit against external applied voltage | max. 12V (30V for 1s) |
Settling time for ohmic load | 0.25 ms |
Settling time for capacitive load | - |
Settling time for inductive load | 1.5 ms |
Resolution in bit | 12 |
Conversion time | 2 ms all channels |
Substitute value can be applied | no |
Output data size | 4 Byte |
Status information, alarms, diagnostics |
|
Status display | yes |
Interrupts | no |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | yes |
Diagnostics information read-out | possible |
Supply voltage display | green LED |
Group error display | red LED |
Channel error display | red LED per channel |
Isolation |
|
Between channels | - |
Between channels of groups to | - |
Between channels and backplane bus | |
Between channels and power supply | |
Max. potential difference between circuits | - |
Max. potential difference between inputs (Ucm) | - |
Max. potential difference between Mana and Mintern (Uiso) | DC 75 V/ AC 50 V |
Max. potential difference between inputs and Mana (Ucm) | - |
Max. potential difference between inputs and Mintern (Uiso) | - |
Max. potential difference between Mintern and outputs | - |
Insulation tested with | DC 500 V |
Datasizes |
|
Input bytes | 0 |
Output bytes | 4 |
Parameter bytes | 8 |
Diagnostic bytes | 20 |
Housing | |
Material | PPE / PPE GF10 |
Mounting | Profile rail 35 mm |
Mechanical data |
|
Dimensions (WxHxD) | 12.9 mm x 109 mm x 76.5 mm |
Net weight | 61 g |
Weight including accessories | 61 g |
Gross weight | 75 g |
Environmental conditions | |
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | yes |
KC certification | yes |